Ring Main
/ rɪŋ meɪn /
Also known as: ring final circuit, ring circuit, 13A ring circuit
Definition
A ring main (ring final circuit) is a wiring arrangement - largely unique to the UK - where a single 2.5mm² cable starts at a 32A MCB in the consumer unit, visits each socket outlet in turn, and returns to the same MCB terminals. The cable forms a complete loop, giving each socket two current paths back to the MCB. This halves the effective current in each cable section, allowing 2.5mm² cable to safely feed a 32A breaker with a maximum circuit load of 7.2kW.
In practice
A standard domestic property has two ring main circuits - one for the ground floor sockets and one for the upper floor - each protected by a 32A MCB with RCD protection. The circuits serve all 13A socket outlets on their respective floors. Dedicated radial circuits (not rings) are used for higher-load equipment: cooker (32-45A), shower (32-40A), dishwasher, and washing machine (typically 16A or 20A).
Additional sockets may be connected as spurs from the ring. An unfused spur may feed only one single or one double socket. A fused connection unit (FCU) with a built-in fuse can feed a further radial circuit. The most common fault found on existing ring mains in older properties is a missing return - the ring is incomplete and effectively a radial, overloading the cable. This is detected by the ring continuity test carried out as part of an electrical inspection.
Building Regulations
BS 7671 Appendix 15 covers the design and installation of ring final circuits. Adding a socket or extending a ring main is notifiable work under Part P if it involves a new circuit or circuit extension in certain locations (kitchens, bathrooms, outdoors). Adding a spur to an existing ring is typically self-certifiable minor works that requires a Minor Electrical Installation Works Certificate (MEIWC) from the electrician.
Full Building Regulations guidanceSee also