Fire Damper
/ faɪə ˈdæmpə /
Also known as: ductwork fire damper, curtain fire damper, combined fire and smoke damper
Definition
A fire damper is a passive fire protection device installed within ventilation ductwork at the point where a duct penetrates a fire compartment wall or floor, closing automatically in a fire to prevent flames and hot gases spreading through the duct from one compartment to another. Specified to BS EN 15650; classified by fire resistance period (typically E30 or E90 integrity). Triggered by a fusible link (melts at 72 degrees C, releasing spring-loaded blades) or electrically from the fire alarm. Distinct from a smoke damper (closes on smoke detection at lower temperatures, or via the alarm system) - combined fire and smoke dampers perform both functions. Required by Approved Document B wherever ductwork penetrates a compartment boundary (subject to duct size thresholds). Must be tested annually (or 6-monthly in high-risk environments) with proper access provided - inaccessible dampers cannot be tested or maintained.
In practice
The biggest practical issue with fire dampers is access for testing. When ductwork is designed and installed, fire damper locations must be identifiable and accessible - either via an access panel in the ductwork close to the damper, or via a ceiling access hatch in a suspended ceiling where the damper is above. In many commercial fit-outs, fire dampers are installed in ductwork running through suspended ceiling voids, with no access hatches provided because the mechanical contractor did not coordinate with the ceiling contractor. The result is dampers that cannot be tested and a building that is theoretically non-compliant with BS 9999 maintenance requirements.
When specifying mechanical ventilation for a new building or a fit-out of an existing building, the mechanical engineer's drawings should show all fire damper locations with access provisions noted. This should be checked during design review, not discovered during construction when ceiling layouts are already fixed. Building Regulations Approved Document B and the fire strategy report should identify all fire compartment boundaries crossed by ductwork, and the mechanical engineer should confirm that a fire damper (or alternative fire protection measure) is provided at each location.